This class will cover the use of Autodesk CFD software as a design analysis tool to provide an effective, engineered smoke-control strategy for a shopping mall of large and complex geometry. We'll examine how fire dynamics were modeled and how important aspects such as smoke propagation and temperature distribution were investigated. The participants will learn about smoke movement in far greater detail than is possible through traditional design tools, such as zone models and algebraic equations, and we'll cover the impact of irregular shapes and unusual air movements that could not be addressed otherwise. We'll demonstrate how we can design the smoke exhaust systems to maintain a prescribed smoke-layer height, tenable temperature, and smoke visibility; and how we can optimize the volume of smoke to be exhausted to meet life-safety goals. Based on the Autodesk CFD results, we'll show how we can draw important conclusions and introduce valuable recommendations to minimize smoke hazards.

주요 학습

  • Discover how fire dynamics can be modeled and analyzed using Autodesk CFD
  • Learn how to highlight key results from Autodesk CFD for life-safety assessment in a building of large and complex geometry
  • Draw important conclusions and valuable recommendations to minimize smoke hazards
  • Look for potential insight to optimize smoke exhaust system design and layout by analyzing different fire scenarios

발표자

  • Munirajulu M
    Dr. Munirajulu. M, Bachelor of Technology (Hons.) and Ph.D. from IIT, Kharagpur, India, has more than 27 years of industry experience using CFD technology for design of HVAC, Automotive, Fluid Handling Equipment, Steam power plant products. He has been with Larsen & Toubro Limited since 2005 and prior to this, he has worked with ABB Limited and Alstom Projects India Limited for about 9 years. Currently he is responsible for performance based design using CFD analysis in MEP/AEC areas related to commercial buildings and airports in L&T Construction, Larsen & Toubro Limited, Chennai. He has been using Autodesk CFD Simulation software for MEP/AEC applications in areas such as data center cooling, thermal comfort, basement car park ventilation, DG room ventilation, rain water free surface flow for airport roof design, and smoke simulation in buildings in design stage as well as for trouble shooting. He has been a speaker at AU since 2017 through 2022, both in USA and India.
Video Player is loading.
Current Time 0:00
Duration 56:41
Loaded: 0.29%
Stream Type LIVE
Remaining Time 56:41
 
1x
  • Chapters
  • descriptions off, selected
  • en (Main), selected
Transcript

DR. M. MUNIRAJULU: I'm glad you could make it to my session in time, and I appreciate-- are you enjoying AU here?

AUDIENCE: [INAUDIBLE]

DR. M. MUNIRAJULU: OK, good. I am a first timer here, both attending and presenting. And after two days of hectic walking around and attending various sessions, I have started to love AU. Yeah. The title for my topic today is "Life Safety using Autodesk CFD." If I'm fast, let me know. I'll try to go slow. I'm going to talk about two or three important outcomes from Autodesk simulation CFD in the design of safe buildings, especially life safety.

OK. Let me introduce myself. My name is Munirajulu. I don't know how many of you will be able to pronounce my name. But in short, we can remember call me as Muni, M-U-N-I. Is that OK? Fine? Yeah. Thank you.

In India, when somebody meets another person for the first time, when they get into conversation, they ask a lot of questions. Where are you from? Where do you work? And then, are you married? And how many children you have. So that is a kind of a culture we have.

So let me introduce myself also in that way. I'm married for the last 20 years, and I have a wonderful family, my wife and two daughters. On the professional front, I am an engineer by qualification, as well as experience. I'm a kind of a CFD technology savvy. For the last 21 years, directly or indirectly, I've been involved with the application of CFD. I have worked in varied industries, products ranging from steam turbines, steam boilers, automotive, [INAUDIBLE].

And I like to keep up with the new technologies, the technology trends. So a few months back, I got myself certified as a IoT professional, Internet of Things. So there is no connection between CFD and IoT right now, but that is my interests. And as I told you, I've been working in the engineering and R&D setup and mainly using CAD, FEA, CFD. OK. Currently I'm chief engineering manager in Larsen & Toubro Limited, India.

OK, real quick information about the organization I work for. Larsen & Toubro, or L&T, is a US dollar $17 billion in revenue. It's a technology, engineering, construction, manufacturing, and financial services conglomerate, with global presence. We are into key sectors-- hydrocarbon, infrastructure, power, process industries, defense. And L&T construction, which is a construction arm of L&T, is India's largest construction organization. And we are ranked among the world's top 30 contractors in that space.

OK. Let me ask you this. How many of you have been to India? Nobody. OK, how many of you are planning to at least visit India, maybe desire? OK, that's good. That's good. Thank you. Thank you.

L&T as constructor designed and built major airports in India. When you visit India, when you land up in Delhi International Airport or the Mumbai International Airport, or Hyderabad Airport, and those airports are designed and built by L&T.

And how many of you are in information technology business? Many of you. Yeah. And you know from India, we have major IT business providers-- TCS, Cognizant, Wipro, and Tech Mahindra, companies like this. And when you visit those companies, to their business facilities, to their offices, you will see landmark structures. So these were designed and built by L&T. OK.

The key word for today's topic is safety. I'm worried about what will ensure safety of people in a commercial building, such as a retail shopping mall, in the event of fire. And that will be based on the application of Autodesk CFD as a design and analysis tool.

I have split my presentation into four parts, four key objectives, learning objectives. And these are based on the CFD project that we have done in the design of a retail shopping mall for India. And one more thing I forgot to tell is that currently we are building Al Rayyan Stadium in Qatar, which would be used for FIFA 2022 World Cup. If you happen to be there, you can remember this. OK.

The four objectives, they cover the fired dynamics modeling. And we will look at key results in terms of life safety assessment, then some conclusions and recommendations that we can draw from. The fourth objective would cover an attempt that we have made to optimize smoke exhaust system design by analyzing different fire scenarios.

Class summary. I'm not going to go into details, but I'll give you an highlight. For smoke inhalation, there are other analysis software available in the market. But here we have chosen to use Autodesk Simulation CFD because our building design data, the 3D models and drawings, we are using Revit for producing 3D models and drawings. So to take advantage of the interface between Revit and CFD, we have chosen Autodesk Simulation CFD.

And as some of you know, CFD is not done for all cases. CFD is done-- analysis is done-- when a building is large, and the geometry is complex. Because there, if the building is large and the geometry is complex, the traditional techniques will not be-- you will not be able to use it for life safety assessment. OK.

OK, before we jump into the details of what we've done, I would like to go through some basics. Because understanding these basics would help us to relate to why we have done what we have done. So these basics are about what is fire-- fire triangle, tetrahedron, and stages of fire. What is fire dynamics? How does fire spread? How do we quantify fire? And then classification of fire.

For some of you, these are very, very basics. But still, I would like to go through quickly. For some of them, I'll give highlights. And some of them, I'll give some more details. OK. Sorry about that.

What is fire? OK, all of you know, if you sit in front of a fire, you feel the heat, and then see the light. But from the engineering perspective, fire is basically a exothermic chemical reaction that produces heat and emits light.

And how do we quantify fire? During fire, heat energy is released. And the rate of release of energy is called HRR. And this is also called fire power. And this quantity is very important because this is an important input into the CFD analysis for the fire source.

Classifying fire. Fire is classified into different types-- A, B, C, D, K. I'll not go into the details. It is there in the handout you can go to later on in the web link I have given, and that will give you more details. This fire classification is based on the type of fuel that burns. And this also helps us basically to decide what kind of a metric to use for preventing or suppressing fire.

Now details about some of them. Fire triangle, when fuel, heat, and oxygen come together, fire starts. So the geometrical representation of that is basically fire triangle. Now, once fire starts, for it to exist and continue to exist, we need a fourth element, which is a chemical chain reaction, uninhibited chemical reaction. So when these four elements are geometrically represented, that is called fire tetrahedron.

Now why I'm showing this is for preventing fire or suppressing fire. If one of them is eliminated or one of them is reduced, fire prevention or suppression happens. So to highlight that point, I have put these pictures here.

Stages of fire. Fire starts at ignition and grows as more and more fuel is burned and reaches a peak value of heat release rate and also temperature when all of the fuel has caught fire. And after the available fuel has caught fire, the intensity reduces, and fire basically decays. This is a traditional fire development curve in terms of temperature and time.

Why this is important, and why I'm showing it here, is because for designing smoke exhaust systems, we design fire, whether it is a steady state that means the heat release rate doesn't vary with time, or unsteady state fire, that is heat release rate varies with time. So one of these two approaches are taken. And in CFD also, we have to use one of these approaches. So it is important to understand what kind of a fire growth we are considering in the analysis.

OK. Once fire starts, how does it spread? So fire spreads by heat transfer. And heat transfer plays a very critical role in ignition, growth, decay, and extension of fire. And as you know, heat transfer takes place by induction, convection, and radiation. Heat from fire, while it is spreading by conduction, basically it spreads to the solids.

For example, in building, building elements like walls, structural elements, so that heat transfer through the solids is called conduction. Heat from fires spreads by convection, that is moment of hot gases. For example, hot smoke close to the fire and to a region away from the fire, or hot air moving from a hot environment to a colder environment. This is called fire spread by convection.

Then finally, fire spreads by radiation also. Heat from the fire spreads by electromagnetic radiation. Some of these already you would know it, but I'm presenting this here so that it would relate to actually what we are going to see with the smoke analysis.

All right. So we have seen what is fire and how fire grows, and now it's time to look at why we are interested in the fire. Fire releases heat energy, and temperature is a measure of that heat energy. And the human body, human skin, responds to temperature exposure in different ways.

I have put up this information here. For example, 44 degrees Celsius, the human skin begins to feel pain. 48 degrees, first degree burn injury. 55, the human skin receives a second degree burn injuriy. 62, that is a kind of a limit where human tissue, the burned human tissue, becomes numb.

So when fire happens, from the point of view of life safety, the temperature exposure to human skin is very important. So that is the reason I'm giving this data here. I've taken this information from NIST. So the weblink has been given there.

And fire also releases smoke. Smoke contains toxic gases, like carbon monoxide, hydrogen cyanide. And this bar chart shows most deaths during fire happens by smoke inhalation, rather than by burns. Almost 2 to 3 times of deaths during fire happens because of smoke inhalation, compared to smoke burns.

Apart from human loss or personal loss, there is an economic loss. Here, I'll put up an information about the total cost of fire. This is in 2011 data, roughly 2.1% of US GDP goes into managing the total cost of fire. And the stabilizer split up of various components. If you are interested, you can go to this website, [INAUDIBLE], or in the handout, I've given these details.

Fire loss in the US. This pie chart shows during 2016, 74% of the fires are structure fires, meaning the fires that happen in residential buildings and commercial structures. This is 2016 data, again from NFPA.

OK. This infographic I have put here to show that fire and its consequences are a around the clock concern for us. For example, here one structure fire was reported every 66 seconds, based on 2016 data in the US. And then one home fire every 90 seconds. And then one highway vehicle fire every three minutes. So it is a kind of around the clock concern if fire happens.

OK, knowing that, there are consequences to fire. And what do we do? Can we do something to mitigate it when it comes to building? Yes, we can do it. In the design and development stage itself, we can use proper tools. And we can use Autodesk Simulation CFD to simulate the smoke movement and temperature development in the building for life safety assessment. OK.

When we use design analysis tool like Autodesk CFD, a key challenge is, how do we represent a real fire into the software? How do digitally represent that real fire in the software? In Autodesk, the five source is represented as a fire part. And what is fire part? Fire part is nothing but it's a CAD part, a short cylinder enclosed in a steel ring.

And this fire fire part is assigned a resistance material, meaning it has some porosity. And this fire part is kept little above the floor to allow for the air to flow in to simulate the smoke movement. That is, flow enters and leaves through the bottom of the top surface of this fire part. That is why the enclosing steel ring is kept to ensure that.

OK. Now into the details of a real project, for which we have done the CFD. This is where the rubber meets the road. We have done the CFD analysis for a retail shopping mall. This is, again, a transit-oriented development project already completed, designed and developed by L&T in Mumbai in India. So here, this is the ground level entrance to the shopping mall,.

And this is where our replacement air, our fresh air, will enter in case of fire. So that is represented in the CFD model in terms of a CAD part. Of course, we have taken the CAD geometry from the Revit, and then we have done simplification suitable for CFD. And this retail mall building has upper ground and two levels, G plus 1 and G plus 2.

You have a large central atrium. And on either side, you have three small atriums in this retail shopping mall. A little bit more details to understand the geometry of this building. So here I've given the sectional details. Upper ground level, G plus 1 and G plus 2. Here I have indicated location of the fire that is on the ground.

And this hatch portion here, that represent the corridor space where people will be moving during shopping. And they also become exit paths when the fire event. This x- and y-plane I have indicated to show that the CFD output we have taken on these planes, the visualization of the CFD results we have taken on these x- and y-planes passing through this fire.

Now, if you look at the G plus 1 and G plus 2 sections, you'll see that, again, you have hatch portions here, and again hatch portions here. These are all corridors meant for people walking around the shopping mall. Then this [INAUDIBLE]. They are the wide spaces. Basically, they provide interconnecting spaces from the upper ground to the G plus 1 to G plus 2 to the atrium ceiling, the roof.

This is a 3D section again. This gives a better view of the building geometry. You have the fire kept on the ground, and then you have the corridors for people to walk on all the levels-- 2G, G plus 1, and G plus 2. The atriums are covered by skylights.

OK. After looking at the CAD part of it for CFD, now we will get into how we model the fire in Autodesk CFD. Here we have assigned a resistance property to the fire part with a free area ratio of 0.85 Wife and high thermal conductivity, a value of 200 watt per meter per Kelvin.

And in the Resistance Direction menu in the property settings, we have indicated floor direction as global z. This is basically-- software doesn't know whether the smoke will go up or down. So we have to specify the expected direction of the smoke flow in the software.

And the fire source has been shown to grow as a fast I-squared fire growing up to 2.5 megawatts, and then remain steady. And we have used convective portion of that heat release rate. The reason being, why convecive portion alone, that is about 70% of the total fire char. Because the smoke generation and the moment is controlled by the convective portion of the heat release rate. That's why we have taken only 70% in this model.

And since it is a time dependent fire, we have given a time code to indicate that the heat release rate is dependent on time. Mesh details, very important. If some of you don't know what is a mesh, for example, this room, this white space is filled by air. And this space will be divided into small blocks. And in each block, these flow and panel parameters will be calculated by the software. And that is what we call as a mesh.

And we are able to give very fine mesh in the fire part. Here, we have given a uniform mesh of five elements. And also to capture the flow below the fire part, because the fresh air will enter underneath here. So there also we have to give mesh refinement. And since smoke is expected to grow and develop a column of smoke, to accurately predict the smoke development and the spread, about this fire also we have given the regional mesh refinement in Autodesk. The sold ring is suppressed basically to indicate that we are constraining the airflow to take place only from the bottom of the fire part to the top of the fire part.

Material properties. Since fire is involved here, temperatures are high. And buoyancy effects will come into picture. So we have given density variation with temperature. Boundary condition. Now, for the volume occupied by air in a building is the [INAUDIBLE] domain. It will have inlets and outlets. So at inlet, I have specified temperature, pressure, and a scalar boundary condition. These temperature and pressure are basically ambient conditions for [INAUDIBLE] condition in Mumbai.

The scalar value of zero here, this indicates that we are specifying at the inlet, the air is fresh. That means it doesn't have any contaminant or smoke or whatever it is. Now, the outlet boundary conditions. Outlet boundary conditions are given at the smoke exhaust fan locations. And we have considered the fans only in the zone 2 here. I'll come to that later on. And I have indicated here what is the fan capacity for each fan number.

OK. After having created a CAD geometry for CFD and then assigning the fire part properties, now we have to-- based on objective of the CFD analysis, we have to specify the solution parameters. And one of them is whether we are doing a transient CFD analysis or a steady state CFD analysis. So here in the solution mode, we specify as transient. And in result quantities, we have switched on smoke visibility because we want the smoke levels in this building for life assessment.

And when we are switching on the smoke visibility, we have to provide the smoke visibility parameters, given here. It depends on what type of combustion, for a flaming combustion is the value. And this is the signage constant, whether it's an illuminated signage or a reflective signage. And this is a [INAUDIBLE]. [INAUDIBLE], we have taken an average of [INAUDIBLE] polyurethane form for a fuel package of typically a kiosk fire and a sofa fire.

And our objective is to simulate smoke and smoke temperatures. Both fluid flow and heat transfer would be involved. So we have switched on flow and thermal in the physics menu here, [INAUDIBLE] menu. And in Autodesk CFD, smoke concentration is calculated as a scalar quantity. And it doesn't give exact values of the smoke concentration, but it gives you a scalar quantity. So we have to switch on general scalar on and specificy diffusion coefficient.

And this diffusion coefficient value we have taken based on the Autodesk CFD best practice suggestions. And this value is not very critical, but it's good to keep a approximately relevant value here.

OK, initial conditions, since it is a transient simulation, we have specified initial condition of scalar 0, means it is smoke free initially, and then temperature of 32.5 degrees.

OK. So having looked at how we model the CAD geometry and how we specify the solution parameters, the fresh air properties and smoke exhaust fan capacities, the meshing details, it is time to look at key results. For a designer, the most important key results are smoke free space and tenable smoke temperature for people to escape during the event of fire. The smoke free space is defined as a space where the visibility is more than 10 meters, more than or equal to 10 meters.

And the tenable limit for temperature is taken as 60 degree Celsius based on the BS standards. And Autodesk Simulation, as I told you, doesn't give the [INAUDIBLE] concentration for the assessment of toxicity levels. But the standards mention that toxicity is deemed acceptable if visibility is greater than 10 meters. So we will focus only on the smoke visibility and the smoke temperature as parameters for life assessment in the building.

OK. Key result one, smoke visibility. I have given here smoke visibility plots in the z-plane, which is 1.8 meter above the G plus 2 floor. That is basically the walking height for the people in the G plus 2 floor. And y-plane is basically a vertical plane on which I've given the visibility level values.

So here you see that the visibility values are greater than 10 meters below this 1.8 meter height, meaning this is occupied space for the people moving around in the shopping mall and, the smoke levels are actually above that. So this plot is at about 19 minutes. So people actually would easily escape during that period. And here also you see the walking corridors are free from smoke. These are the walking corridors.

Key result two, smoke temperature. We are looking at a tenable smoke temperature. Here again, the colorful plots-- x-plane, y-plane-- if you look at the values below this red line, these temperatures are below 60 degrees, which is OK.

Key result three, very important. What determines the smoke movement and smoke spread? And related to that, the smoke temperature levels is how this airflow field develops within the building in the event of the smoke fans coming into operation and fresh air being drawn. So here I have shown just near the fire part, the vector plots, and also what happens to the air flow field at the entrance to the shopping mall, which becomes an exit when people are actually coming out.

So here, the standards mention that if the air contracting the smoke plume is more than 1 meter per second, the smoke plume actually will get deflected, and it will disperse into the occupied spaces, which is not good. Here, in the results that we have got is again 19 minutes, at 19 minutes from the start of the fire. So here you see that the airspeed conducting-- or the average velocity conducting the smoke plume here-- is 0.8 meter per second.

Now, when people are exiting through the doors, the fresh air is being drawn in the opposite direction. People are going like this. Fresh air will be coming in. And if this replacement air velocity is more than a certain value, it will hinder the people movement. It will obstruct the people movement. So the BS standard mentions 5 meters per second as the limit for unhindered escape through the exits or the exit doors. And what we've got here is much less than that. So here we have 1.6 meters at the entrance, and down the line we have 1.4 meters. This is acceptable.

OK. So far, the key results I have presented only at a time close to the escape, and there's 19 or 20 minutes I have presented these results. But for a regulator or a designer, the information about these three quantities-- smoke movement, temperature levels, and the air flow field-- these values, these levels, are important throughout the escape time. That is, from the moment of start of fire until the 20 minute escape time.

So I'm going to present to you some details how the smoke develops and how it spreads during that time. OK. These are the smoke visibility plots in the x-plane. I have given the results at various times. 30 seconds, it is just trying to develop. The black area is basically smoke filled area, and the remaining areas are smoke free in this picture. That is, this is the smoke filled area, and the remaining areas do not have any smoke.

And then at about one minute, the smoke rises to the atrium ceiling, and it starts accumulating there as a reservoir. Then from one minute down to 19 minutes, the smoke continues to rise. And it also starts coming down. But what we have seen is, it has not yet started coming down, even at 19 minutes, to the occupied level. So this kind of information, you will get it when you are evaluating the smoke levels from CFD, Autodesk CFD.

This is more clear in the y-plane. So here you will see at about three minutes, the smoke starts getting exhausted here from the exhaust fans. OK. And as time continues, smoke would go out, get exhausted. And some amount of smoke also starts coming down. This is because there is a balance happening from the quantity that is being exhausted by the smoke fans and the momentum-driven flow that happens because of the smoke rising due to high temperature levels.

And again here, the smoke levels are not coming down below the 1.8 meter level. That is where we consider the occupied height in the G plus 2 floor. OK. This gives a nice picture about what happens to the smoke at 1.8 meter level. This level, if you look from the top, this is how the smoke visibility values will look like.

And here, you see that throughout the-- from the fire start to the end of the 20 minute period, these corridor spaces are free from smoke. Of course, this is a column of smoke, which is represented as circle when you take the horizontal plane. So this indicates that when people are moving from the start of the fire until 20 minutes, people can easily escape from this building. They can at least reach the exit staircases.

OK. And second most important result is temperature development. Just like we saw smoke development with respect to time, we can also track how the temperature levels exist during the course of this fire. 30 seconds, just smoke getting hot, and then the temperature keeps on increasing. But one thing I would like you to notice is this-- sorry.

This high temperature smoke is confined to only the atrium. It is not getting into the occupied areas. See here, here, these occupied areas, temperature values are not very high. So only in the atrium, the high temperature smoke is rising and reaching the ceiling and then getting exhausted.

Again, on the y-plane, a similar result. But this gives a better visualization with respect to the temperature levels. And you'll see that below 1.8 meter level, temperatures are less than 60 degrees, which is our requirement.

OK. This fresh air flow moment with respect to time again on a plane, which is on a z-plane, which is close to the fire on the ground floor. Actually, this airflow field is very important, as I told you, for the smoke development and movement. At about one minute, the fresh air is getting drawn. And by about three minutes, this airflow field gets stabilized. And from three minutes down to 20 minutes, this airflow field will more or less remain the same.

Why I am showing this is, if this airflow coming in contact with a plume changes, or if it has higher values for some reason, then what it would indicate that at that particular point of time, the smoke has a potential to deflect and get dispersed. So that is the reason I'm showing this airflow field near to the fire location.

This is in more detail. Here you see that it's a vector plot. This is a kind of beautiful results. You will get it from Simulation CFD. This is the smoke plume vectors. And the fresh air coming in contact is shown in the red arrows. And you see that at each level-- UG level, G plus 1, and G plus 2, this fresh air is coming towards the plume, which means it will not get deflected or dispersed.

OK, I just want to summarize. What we see from this analysis is a well-defined smoke plume. And it is rising towards the smoke exhaust fans. And another thing we saw is that make up air doesn't disturb the smoke plume. So no smoke dispersion or visibility problems. And hot smoke temperature is below 60 degrees, which is within the acceptable limits for human safety.

Some conclusions. The smoke exhaust fan capacity and layout is adequate to provide a smoke free space for 20 minutes. And based on the smoke exhaust fan layout and fire zoning logic, the CFD analysis using Autodesk CFD can accurately predict smoke development, smoke movement, visibility levels, temperature distribution. Hence, this approach can be used to validate the ventilation design for anticipated fire scenarios.

And one other thing is, the fire engineers have to actually do some fire zoning first before we take up the CFD analysis. Because if we don't do the fire zoning, and you go by some prescriptive-based design, it may not work. So we have to do some kind of fire zoning first, and then we can use the CFD to optimize this fan layout.

OK. This is the last part of my presentation. We get a lot of insights from CFD analysis-- how the smoke is produced, how it grows, and how it spreads, and what are the temperature levels, and how the air flow field happens, and things like that. But as an engineer, it is important how we use that information. And basically, use that information for optimizing the design.

I'll just show one attempt that we made to optimize the design. Two things we have to remember here. Smoke ventilation is created by the mechanical ventilation fans kept at the higher level. And the fresh air enters at the ground level or the lower level. And then the prior distribution of smoke or air velocity is not known for any given design at the podium level. So therefore, you have to actually consider simulating more than one scenario to complete an optimized design.

Here, design one and design two. Design one is our initial design, and design two is a final design, optimized design. In design one, what we have considered is the entire building on the right side-- that is zone R-- is considered as one zone, and then this one is considered as another zone. And accordingly, smoke fans were designed and kept here.

What happens is, anywhere fire happens in this zone, all these fans will get activated. And in this case, we have divided into a smaller number of smoke zones or fire zones. And if fire happens or detected in any one zone, the fans get activated only in that zone. So I have given the fan capacity in these tables for design one and design two.

At this stage, I would like to mention a very useful tool for optimizing smoke exhaust system design. This is AtriumCalc version 1.1 by John Klote. And based on the design fire size and outdoor ambient temperature, and the height from the base of the fire to the smoke layer interface, with these three inputs, this spreadsheet calculation will give you the volume of smoke to be exhausted based on the fire size. And not only that, the number of fans and the layout can be decided to a wide plug holing. So all these calculations are available in this spreadsheet, and it's very useful.

OK. We'll just compare the results for design one and two. In design one, you see that smoke gets actually deflected towards the right, and then it starts entering the G plus 1 here, G plus 1, here G plus 1 and G plus 2 levels. Whereas in design two, it just rises in the atrium space here. It just rises straight. It doesn't get deflected or dispersed.

This is on the z-plane at 1.8 meter level above the G plus 2 floor. And here you see that by about four minutes, the corridor space is already filled with smoke, meaning the visibility is very less here. Whereas in the design two, the corridor spaces are free from smoke. By about 10 minutes, the corridors are getting filled, and visibility is affected here. But whereas here, in this design two, we don't have any problem. Visibility levels are about 10 meter.

Here we compare the results for temperature, smoke temperature for design one and design two. Again, if you look at design one, because the smoke plume gets deflected, there is a risk that high temperatures can exist in the occupied spaces. Whereas in design two, you don't have that problem. And if you look at the airflow fields, again, this airflow field shows it is getting deflected. And here it is not.

And if you look at the horizontal planes here, you'll see that the air conducting the smoke plume is more than 1.8 meter, whereas here it is 0.8 meter. So that itself actually indicates that in design one, there will be visibility problems. There will be a problem for people to escape because smoke starts getting deflected and dispersed into the occupied space.

This is, again, a comparison of airflow field for design one and design two. Design one, you have the average velocity conducting the plume more than 1 meter. In design two, we have 0.8. And here you see in the design one, the fresh air coming in contact with the plume is very erratic. It is coming towards and also going away from it. Whereas here, the fresh air coming in contact with the plume is always towards it. This ensures that the smoke will rise nicely like a column of smoke to the atrium, whereas here it doesn't. It will get spread. It will get deflected.

OK. Just to conclude the optimization exercise, what we see-- basically, we compare three parameters-- the smoke visibility is one-- and here we see in design one it is not acceptable. In design two, it is acceptable. And second parameter, smoke temperature, in design one it is risky because the smoke temperature can be-- hot smoke can get into the corridor spaces. And in design two, it is below 60 degrees. It is acceptable.

Then airflow field, for design one not acceptable. Design two, it's acceptable. So if we want to conclude about the smoke exhaust system design and layout, for design one it is not suitable. But in design two, it is adequate. Adequate to provide the smoke visibility and tenable temperatures throughout the escape time of 20 minutes.

OK. Now it's time for any Q&A. Any questions? Yes.

AUDIENCE: How big was the model?

DR. M. MUNIRAJULU: How big was the model?

AUDIENCE: [INAUDIBLE] mesh size.

DR. M. MUNIRAJULU: Mesh size, yeah. We tried various mesh sizes. Initially we just did the analysis maybe 6 million. And then to get proper results, we went to 12 million. And then finally, I think we concluded this project using about 24 million. Yeah, it's quite extensive. It's very mesh intensive work. This program would run for two, three days continuously to get results. Yeah.

AUDIENCE: So you mentioned that you [INAUDIBLE] Revit [INAUDIBLE] detailed. You said something about the efforts to get the Revit model in a less detailed [INAUDIBLE]?

DR. M. MUNIRAJULU: Actually, when the Revit model is exported into Autodesk CFD, you would get all the details. But you may not get the CFD volume that you're looking for. OK? Because there would be some gaps in the actual Revit model. And there will be some details that you may not require, which will create meshing problems in the CFD volume. And there will be components which will be intersecting, which will be sitting on edges and things like that.

So it is-- we have tried both. For a simple geometry, we just could get directly into the CFD. But for this geometry, we had trouble. And what we did is we used the existing Revit model to redo wherever we have problems. After creating the CFD volume-- actually, while creating the CFD volume, we come across some problems. At that stage, we would actually modify some walls or the intersection between the floor and the wall and the ceilings and things like that. So we had to do a lot of correction to get this CAD geometry. It's not easy. I'm not telling that it is 100%. You can just get it [INAUDIBLE]. Yeah, it involves effort. Yeah.

AUDIENCE: Did you have to check different fire locations, or [INAUDIBLE]?

DR. M. MUNIRAJULU: Sorry, I didn't get your question.

AUDIENCE: Did you have to check different fire locations where the fire is located?

DR. M. MUNIRAJULU: Yeah. Yeah, we tried I think two or three fire locations. And I'm not a designer. I am basically an analyst. And the designers decided-- they anticipated our probable fire location as something that we have used here. Yeah. So we have analyzed various fire locations. Yeah. Yeah.

AUDIENCE: [INAUDIBLE]

DR. M. MUNIRAJULU: Yeah. Yeah. We have taken the fire to grow as a fast t-squared fire. That fast t-squared, how it grows with time, that decay we have taken it from NFPA 92B. There is a constant, and the convective portion of the heat versus the time, it's basically q is equal to some constant t square. So that constant is there in the NFPA. And for some fires, some real data is also available. So it is up to us to use a kind of realistic data.

So that's what I can say, yeah. There are three types of fire growth, slow, medium, and fast t-squared. So here, we have taken fast t-squared, NFPA 92B. So using that equation, we can actually decide the-- it's not a linear variation. It's actually more like a [INAUDIBLE] goes like this, like a parabola. Exponential, yeah. Right.

AUDIENCE: Question over here. So I'm not used to using [INAUDIBLE], so I'm just curious about the software, and using other [INAUDIBLE]. And I'm curious about the validation [INAUDIBLE] validate it for various simulation [INAUDIBLE].

DR. M. MUNIRAJULU: Yeah, correct. So let me make this clear. We don't use-- we don't validate the software. We use a software to validate the design. That is number one. And number two is, which is relevant with respect to your question-- for example, the smoke development and movement, we have taken one reference for which the data is available. It's basically a standard room with a fire size. And we have used that reference basically experimental data.

And then we did the same analysis using Autodesk Simulation CFD. And we have compared the smoke levels and the values. So with that kind of a exercise, we went ahead using the Autodesk CFD. I can share that result with you if you want later on. Yeah.

AUDIENCE: Sure. [INAUDIBLE].

DR. M. MUNIRAJULU: Sure, yeah. But validation cannot be done for a large complex geometry. It can be done only if you have the data for whatever building it is.

AUDIENCE: [INAUDIBLE]

DR. M. MUNIRAJULU: Yeah, correct, yeah.

AUDIENCE: [INAUDIBLE]

DR. M. MUNIRAJULU: Yeah. Another way to do it is basically you do the same thing in FDS [INAUDIBLE] or some other software and see how you get the results. Yeah. Yes. Somebody there. OK.

AUDIENCE: I just [INAUDIBLE].

DR. M. MUNIRAJULU: All right. Yeah, yeah. OK. Any more questions? Any more questions? OK.

So thank you so much, and I request you to give the feedback to me because if you want me to come next time to AU, definitely I need your feedback. OK. Right. And thank you for listening, and let's keep in touch because we can share a lot of information, and [INAUDIBLE] new tools and new approaches. And we can share information. We can try to solve each other's problems.

So my email address is given here. And if you want to know about my company, what we do and stuff like that, the website is given. We can go through the website. And if you want, my visiting card. I'm here. I can give the visiting card to you. So thank you so much once again, and I hope it was useful to you.

[APPLAUSE]

______
icon-svg-close-thick

쿠기 기본 설정

오토데스크는 고객의 개인 정보와 최상의 경험을 중요시합니다. 오토데스크는 정보를 사용자화하고 응용프로그램을 만들기 위해 고객의 본 사이트 사용에 관한 데이터를 수집합니다.

오토데스크에서 고객의 데이터를 수집하고 사용하도록 허용하시겠습니까?

오토데스크에서 사용하는타사 서비스개인정보 처리방침 정책을 자세히 알아보십시오.

반드시 필요 - 사이트가 제대로 작동하고 사용자에게 서비스를 원활하게 제공하기 위해 필수적임

이 쿠키는 오토데스크에서 사용자 기본 설정 또는 로그인 정보를 저장하거나, 사용자 요청에 응답하거나, 장바구니의 품목을 처리하기 위해 필요합니다.

사용자 경험 향상 – 사용자와 관련된 항목을 표시할 수 있게 해 줌

이 쿠키는 오토데스크가 보다 향상된 기능을 제공하고 사용자에게 맞는 정보를 제공할 수 있게 해 줍니다. 사용자에게 맞는 정보 및 환경을 제공하기 위해 오토데스크 또는 서비스를 제공하는 협력업체에서 이 쿠키를 설정할 수 있습니다. 이 쿠키를 허용하지 않을 경우 이러한 서비스 중 일부 또는 전체를 이용하지 못하게 될 수 있습니다.

광고 수신 설정 – 사용자에게 타겟팅된 광고를 제공할 수 있게 해 줌

이 쿠키는 사용자와 관련성이 높은 광고를 표시하고 그 효과를 추적하기 위해 사용자 활동 및 관심 사항에 대한 데이터를 수집합니다. 이렇게 데이터를 수집함으로써 사용자의 관심 사항에 더 적합한 광고를 표시할 수 있습니다. 이 쿠키를 허용하지 않을 경우 관심 분야에 해당되지 않는 광고가 표시될 수 있습니다.

icon-svg-close-thick

타사 서비스

각 범주에서 오토데스크가 사용하는 타사 서비스와 온라인에서 고객으로부터 수집하는 데이터를 사용하는 방식에 대해 자세히 알아보십시오.

icon-svg-hide-thick

icon-svg-show-thick

반드시 필요 - 사이트가 제대로 작동하고 사용자에게 서비스를 원활하게 제공하기 위해 필수적임

Qualtrics
오토데스크는 고객에게 더욱 시의적절하며 관련 있는 이메일 컨텐츠를 제공하기 위해 Qualtrics를 이용합니다. 이를 위해, 고객의 온라인 행동 및 오토데스크에서 전송하는 이메일과의 상호 작용에 관한 데이터를 수집합니다. 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID, 이메일 확인율, 클릭한 링크 등이 포함될 수 있습니다. 오토데스크는 이 데이터를 다른 소스에서 수집된 데이터와 결합하여 고객의 판매 또는 고객 서비스 경험을 개선하며, 고급 분석 처리에 기초하여 보다 관련 있는 컨텐츠를 제공합니다. Qualtrics 개인정보취급방침
Akamai mPulse
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Akamai mPulse를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Akamai mPulse 개인정보취급방침
Digital River
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Digital River를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Digital River 개인정보취급방침
Dynatrace
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Dynatrace를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Dynatrace 개인정보취급방침
Khoros
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Khoros를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Khoros 개인정보취급방침
Launch Darkly
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Launch Darkly를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Launch Darkly 개인정보취급방침
New Relic
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 New Relic를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. New Relic 개인정보취급방침
Salesforce Live Agent
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Salesforce Live Agent를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Salesforce Live Agent 개인정보취급방침
Wistia
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Wistia를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Wistia 개인정보취급방침
Tealium
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Tealium를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Upsellit
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Upsellit를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. CJ Affiliates
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 CJ Affiliates를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Commission Factory
Typepad Stats
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Typepad Stats를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Typepad Stats 개인정보취급방침
Geo Targetly
Autodesk는 Geo Targetly를 사용하여 웹 사이트 방문자를 가장 적합한 웹 페이지로 안내하거나 위치를 기반으로 맞춤형 콘텐츠를 제공합니다. Geo Targetly는 웹 사이트 방문자의 IP 주소를 사용하여 방문자 장치의 대략적인 위치를 파악합니다. 이렇게 하면 방문자가 (대부분의 경우) 현지 언어로 된 콘텐츠를 볼 수 있습니다.Geo Targetly 개인정보취급방침
SpeedCurve
Autodesk에서는 SpeedCurve를 사용하여 웹 페이지 로드 시간과 이미지, 스크립트, 텍스트 등의 후속 요소 응답성을 측정하여 웹 사이트 환경의 성능을 모니터링하고 측정합니다. SpeedCurve 개인정보취급방침
Qualified
Qualified is the Autodesk Live Chat agent platform. This platform provides services to allow our customers to communicate in real-time with Autodesk support. We may collect unique ID for specific browser sessions during a chat. Qualified Privacy Policy

icon-svg-hide-thick

icon-svg-show-thick

사용자 경험 향상 – 사용자와 관련된 항목을 표시할 수 있게 해 줌

Google Optimize
오토데스크는 사이트의 새 기능을 테스트하고 이러한 기능의 고객 경험을 사용자화하기 위해 Google Optimize을 이용합니다. 이를 위해, 고객이 사이트를 방문해 있는 동안 행동 데이터를 수집합니다. 이 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID, 오토데스크 ID 등이 포함될 수 있습니다. 고객은 기능 테스트를 바탕으로 여러 버전의 오토데스크 사이트를 경험하거나 방문자 특성을 바탕으로 개인화된 컨텐츠를 보게 될 수 있습니다. Google Optimize 개인정보취급방침
ClickTale
오토데스크는 고객이 사이트에서 겪을 수 있는 어려움을 더 잘 파악하기 위해 ClickTale을 이용합니다. 페이지의 모든 요소를 포함해 고객이 오토데스크 사이트와 상호 작용하는 방식을 이해하기 위해 세션 녹화를 사용합니다. 개인적으로 식별 가능한 정보는 가려지며 수집되지 않습니다. ClickTale 개인정보취급방침
OneSignal
오토데스크는 OneSignal가 지원하는 사이트에 디지털 광고를 배포하기 위해 OneSignal를 이용합니다. 광고는 OneSignal 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 OneSignal에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 OneSignal에 제공하는 데이터를 사용합니다. OneSignal 개인정보취급방침
Optimizely
오토데스크는 사이트의 새 기능을 테스트하고 이러한 기능의 고객 경험을 사용자화하기 위해 Optimizely을 이용합니다. 이를 위해, 고객이 사이트를 방문해 있는 동안 행동 데이터를 수집합니다. 이 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID, 오토데스크 ID 등이 포함될 수 있습니다. 고객은 기능 테스트를 바탕으로 여러 버전의 오토데스크 사이트를 경험하거나 방문자 특성을 바탕으로 개인화된 컨텐츠를 보게 될 수 있습니다. Optimizely 개인정보취급방침
Amplitude
오토데스크는 사이트의 새 기능을 테스트하고 이러한 기능의 고객 경험을 사용자화하기 위해 Amplitude을 이용합니다. 이를 위해, 고객이 사이트를 방문해 있는 동안 행동 데이터를 수집합니다. 이 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID, 오토데스크 ID 등이 포함될 수 있습니다. 고객은 기능 테스트를 바탕으로 여러 버전의 오토데스크 사이트를 경험하거나 방문자 특성을 바탕으로 개인화된 컨텐츠를 보게 될 수 있습니다. Amplitude 개인정보취급방침
Snowplow
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Snowplow를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Snowplow 개인정보취급방침
UserVoice
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 UserVoice를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. UserVoice 개인정보취급방침
Clearbit
Clearbit를 사용하면 실시간 데이터 보강 기능을 통해 고객에게 개인화되고 관련 있는 환경을 제공할 수 있습니다. Autodesk가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. Clearbit 개인정보취급방침
YouTube
YouTube는 사용자가 웹 사이트에 포함된 비디오를 보고 공유할 수 있도록 해주는 비디오 공유 플랫폼입니다. YouTube는 비디오 성능에 대한 시청 지표를 제공합니다. YouTube 개인정보보호 정책

icon-svg-hide-thick

icon-svg-show-thick

광고 수신 설정 – 사용자에게 타겟팅된 광고를 제공할 수 있게 해 줌

Adobe Analytics
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Adobe Analytics를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID 및 오토데스크 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. Adobe Analytics 개인정보취급방침
Google Analytics (Web Analytics)
오토데스크 사이트에서 고객의 행동에 관한 데이터를 수집하기 위해 Google Analytics (Web Analytics)를 이용합니다. 여기에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 오토데스크는 사이트 성과를 측정하고 고객의 온라인 경험의 편리함을 평가하여 기능을 개선하기 위해 이러한 데이터를 이용합니다. 또한, 이메일, 고객 지원 및 판매와 관련된 고객 경험을 최적화하기 위해 고급 분석 방법도 사용하고 있습니다. AdWords
Marketo
오토데스크는 고객에게 더욱 시의적절하며 관련 있는 이메일 컨텐츠를 제공하기 위해 Marketo를 이용합니다. 이를 위해, 고객의 온라인 행동 및 오토데스크에서 전송하는 이메일과의 상호 작용에 관한 데이터를 수집합니다. 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID, 이메일 확인율, 클릭한 링크 등이 포함될 수 있습니다. 오토데스크는 이 데이터를 다른 소스에서 수집된 데이터와 결합하여 고객의 판매 또는 고객 서비스 경험을 개선하며, 고급 분석 처리에 기초하여 보다 관련 있는 컨텐츠를 제공합니다. Marketo 개인정보취급방침
Doubleclick
오토데스크는 Doubleclick가 지원하는 사이트에 디지털 광고를 배포하기 위해 Doubleclick를 이용합니다. 광고는 Doubleclick 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Doubleclick에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Doubleclick에 제공하는 데이터를 사용합니다. Doubleclick 개인정보취급방침
HubSpot
오토데스크는 고객에게 더욱 시의적절하며 관련 있는 이메일 컨텐츠를 제공하기 위해 HubSpot을 이용합니다. 이를 위해, 고객의 온라인 행동 및 오토데스크에서 전송하는 이메일과의 상호 작용에 관한 데이터를 수집합니다. 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID, 이메일 확인율, 클릭한 링크 등이 포함될 수 있습니다. HubSpot 개인정보취급방침
Twitter
오토데스크는 Twitter가 지원하는 사이트에 디지털 광고를 배포하기 위해 Twitter를 이용합니다. 광고는 Twitter 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Twitter에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Twitter에 제공하는 데이터를 사용합니다. Twitter 개인정보취급방침
Facebook
오토데스크는 Facebook가 지원하는 사이트에 디지털 광고를 배포하기 위해 Facebook를 이용합니다. 광고는 Facebook 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Facebook에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Facebook에 제공하는 데이터를 사용합니다. Facebook 개인정보취급방침
LinkedIn
오토데스크는 LinkedIn가 지원하는 사이트에 디지털 광고를 배포하기 위해 LinkedIn를 이용합니다. 광고는 LinkedIn 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 LinkedIn에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 LinkedIn에 제공하는 데이터를 사용합니다. LinkedIn 개인정보취급방침
Yahoo! Japan
오토데스크는 Yahoo! Japan가 지원하는 사이트에 디지털 광고를 배포하기 위해 Yahoo! Japan를 이용합니다. 광고는 Yahoo! Japan 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Yahoo! Japan에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Yahoo! Japan에 제공하는 데이터를 사용합니다. Yahoo! Japan 개인정보취급방침
Naver
오토데스크는 Naver가 지원하는 사이트에 디지털 광고를 배포하기 위해 Naver를 이용합니다. 광고는 Naver 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Naver에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Naver에 제공하는 데이터를 사용합니다. Naver 개인정보취급방침
Quantcast
오토데스크는 Quantcast가 지원하는 사이트에 디지털 광고를 배포하기 위해 Quantcast를 이용합니다. 광고는 Quantcast 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Quantcast에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Quantcast에 제공하는 데이터를 사용합니다. Quantcast 개인정보취급방침
Call Tracking
오토데스크는 캠페인을 위해 사용자화된 전화번호를 제공하기 위하여 Call Tracking을 이용합니다. 그렇게 하면 고객이 오토데스크 담당자에게 더욱 빠르게 액세스할 수 있으며, 오토데스크의 성과를 더욱 정확하게 평가하는 데 도움이 됩니다. 제공된 전화번호를 기준으로 사이트에서 고객 행동에 관한 데이터를 수집할 수도 있습니다. Call Tracking 개인정보취급방침
Wunderkind
오토데스크는 Wunderkind가 지원하는 사이트에 디지털 광고를 배포하기 위해 Wunderkind를 이용합니다. 광고는 Wunderkind 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Wunderkind에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Wunderkind에 제공하는 데이터를 사용합니다. Wunderkind 개인정보취급방침
ADC Media
오토데스크는 ADC Media가 지원하는 사이트에 디지털 광고를 배포하기 위해 ADC Media를 이용합니다. 광고는 ADC Media 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 ADC Media에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 ADC Media에 제공하는 데이터를 사용합니다. ADC Media 개인정보취급방침
AgrantSEM
오토데스크는 AgrantSEM가 지원하는 사이트에 디지털 광고를 배포하기 위해 AgrantSEM를 이용합니다. 광고는 AgrantSEM 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 AgrantSEM에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 AgrantSEM에 제공하는 데이터를 사용합니다. AgrantSEM 개인정보취급방침
Bidtellect
오토데스크는 Bidtellect가 지원하는 사이트에 디지털 광고를 배포하기 위해 Bidtellect를 이용합니다. 광고는 Bidtellect 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Bidtellect에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Bidtellect에 제공하는 데이터를 사용합니다. Bidtellect 개인정보취급방침
Bing
오토데스크는 Bing가 지원하는 사이트에 디지털 광고를 배포하기 위해 Bing를 이용합니다. 광고는 Bing 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Bing에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Bing에 제공하는 데이터를 사용합니다. Bing 개인정보취급방침
G2Crowd
오토데스크는 G2Crowd가 지원하는 사이트에 디지털 광고를 배포하기 위해 G2Crowd를 이용합니다. 광고는 G2Crowd 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 G2Crowd에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 G2Crowd에 제공하는 데이터를 사용합니다. G2Crowd 개인정보취급방침
NMPI Display
오토데스크는 NMPI Display가 지원하는 사이트에 디지털 광고를 배포하기 위해 NMPI Display를 이용합니다. 광고는 NMPI Display 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 NMPI Display에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 NMPI Display에 제공하는 데이터를 사용합니다. NMPI Display 개인정보취급방침
VK
오토데스크는 VK가 지원하는 사이트에 디지털 광고를 배포하기 위해 VK를 이용합니다. 광고는 VK 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 VK에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 VK에 제공하는 데이터를 사용합니다. VK 개인정보취급방침
Adobe Target
오토데스크는 사이트의 새 기능을 테스트하고 이러한 기능의 고객 경험을 사용자화하기 위해 Adobe Target을 이용합니다. 이를 위해, 고객이 사이트를 방문해 있는 동안 행동 데이터를 수집합니다. 이 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역, IP 주소 또는 장치 ID, 오토데스크 ID 등이 포함될 수 있습니다. 고객은 기능 테스트를 바탕으로 여러 버전의 오토데스크 사이트를 경험하거나 방문자 특성을 바탕으로 개인화된 컨텐츠를 보게 될 수 있습니다. Adobe Target 개인정보취급방침
Google Analytics (Advertising)
오토데스크는 Google Analytics (Advertising)가 지원하는 사이트에 디지털 광고를 배포하기 위해 Google Analytics (Advertising)를 이용합니다. 광고는 Google Analytics (Advertising) 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Google Analytics (Advertising)에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Google Analytics (Advertising)에 제공하는 데이터를 사용합니다. Google Analytics (Advertising) 개인정보취급방침
Trendkite
오토데스크는 Trendkite가 지원하는 사이트에 디지털 광고를 배포하기 위해 Trendkite를 이용합니다. 광고는 Trendkite 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Trendkite에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Trendkite에 제공하는 데이터를 사용합니다. Trendkite 개인정보취급방침
Hotjar
오토데스크는 Hotjar가 지원하는 사이트에 디지털 광고를 배포하기 위해 Hotjar를 이용합니다. 광고는 Hotjar 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Hotjar에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Hotjar에 제공하는 데이터를 사용합니다. Hotjar 개인정보취급방침
6 Sense
오토데스크는 6 Sense가 지원하는 사이트에 디지털 광고를 배포하기 위해 6 Sense를 이용합니다. 광고는 6 Sense 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 6 Sense에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 6 Sense에 제공하는 데이터를 사용합니다. 6 Sense 개인정보취급방침
Terminus
오토데스크는 Terminus가 지원하는 사이트에 디지털 광고를 배포하기 위해 Terminus를 이용합니다. 광고는 Terminus 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 Terminus에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 Terminus에 제공하는 데이터를 사용합니다. Terminus 개인정보취급방침
StackAdapt
오토데스크는 StackAdapt가 지원하는 사이트에 디지털 광고를 배포하기 위해 StackAdapt를 이용합니다. 광고는 StackAdapt 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 StackAdapt에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 StackAdapt에 제공하는 데이터를 사용합니다. StackAdapt 개인정보취급방침
The Trade Desk
오토데스크는 The Trade Desk가 지원하는 사이트에 디지털 광고를 배포하기 위해 The Trade Desk를 이용합니다. 광고는 The Trade Desk 데이터와 고객이 사이트를 방문하는 동안 오토데스크가 수집하는 행동 데이터 모두에 기초하여 제공됩니다. 오토데스크가 수집하는 데이터에는 고객이 방문한 페이지, 시작한 체험판, 재생한 동영상, 구매 내역 및 IP 주소 또는 장치 ID가 포함될 수 있습니다. 이 정보는 The Trade Desk에서 고객으로부터 수집한 데이터와 결합될 수 있습니다. 오토데스크는 디지털 광고 경험에 대한 사용자화를 개선하고 고객에게 더욱 관련 있는 광고를 제시하기 위해 The Trade Desk에 제공하는 데이터를 사용합니다. The Trade Desk 개인정보취급방침
RollWorks
We use RollWorks to deploy digital advertising on sites supported by RollWorks. Ads are based on both RollWorks data and behavioral data that we collect while you’re on our sites. The data we collect may include pages you’ve visited, trials you’ve initiated, videos you’ve played, purchases you’ve made, and your IP address or device ID. This information may be combined with data that RollWorks has collected from you. We use the data that we provide to RollWorks to better customize your digital advertising experience and present you with more relevant ads. RollWorks Privacy Policy

정말 더 적은 온라인 경험을 원하십니까?

오토데스크는 고객 여러분에게 좋은 경험을 드리고 싶습니다. 이전 화면의 범주에 대해 "예"를 선택하셨다면 오토데스크는 고객을 위해 고객 경험을 사용자화하고 향상된 응용프로그램을 제작하기 위해 귀하의 데이터를 수집하고 사용합니다. 언제든지 개인정보 처리방침을 방문해 설정을 변경할 수 있습니다.

고객의 경험. 고객의 선택.

오토데스크는 고객의 개인 정보 보호를 중요시합니다. 오토데스크에서 수집하는 정보는 오토데스크 제품 사용 방법, 고객이 관심을 가질 만한 정보, 오토데스크에서 더욱 뜻깊은 경험을 제공하기 위한 개선 사항을 이해하는 데 도움이 됩니다.

오토데스크에서 고객님께 적합한 경험을 제공해 드리기 위해 고객님의 데이터를 수집하고 사용하도록 허용하시겠습니까?

선택할 수 있는 옵션을 자세히 알아보려면 이 사이트의 개인 정보 설정을 관리해 사용자화된 경험으로 어떤 이점을 얻을 수 있는지 살펴보거나 오토데스크 개인정보 처리방침 정책을 확인해 보십시오.